AWR-160 dust collection ventilation system:

  1. All Envirosystems AWR modules are designed to be located remotely and connected via ducting to a separate fan. Fan volume and static performance is dependent on individual applications. Fans may be supplied by Envirosystems or by others. Several AWR modules may be connected side by side or in multiple banks to provide dust collection volumes of 1,000,000 CFM or more. Although each standard AWR module includes a built in clean air plenum complete with multiple ducting attach points, custom duct attach points or plenums may also be provided for banks of multiple AWR modules. Contact Envirosystems for design assistance.

  2. Air discharged from these filter banks will exceed 40 CFR 63, Sub part GG and may be suitable for re-circulation back into the workplace, or may be exhausted to the outside at the discretion of the customer. Some applications may require additional HEPA or VOC after filter units.

    The AWR module, while custom in nature, is based on the time proven AirWall module design. AirWall units are currently used worldwide for many dust collection applications. Some of the abrasive blasting dust collection applications using the AirWall product for aerospace operations include the Northrop-Grumman B-2 stripping facility in Palmdale, CA, Lockheed-Martin Skunk Works in Palmdale, CA, Large Aircraft Corrosion Control Facility, Tinker AFB, Oklahoma City, OK, as well as many other U.S. Military operations in the U.S. and South Korea (Korea Airlines, Pusan facility).
  3. AWR modules are provided with an automatic reverse pulse filter purging system. This system has a manual as well as an automatic mode. During filter purging, pulses of compressed air automatically clean the cartridges by momentary (1/3 of a second) reverse pressurization. As the pulse dislodges dust from the cartridge exterior, the released dust falls into a collection hopper. The standard hopper is designed to accommodate discharge into a 55 gal drum, but discharge into super sacks can also be provided at no additional charge.

    Optionally there are dust conveying hoppers which allow discharged dust to be conveyed to a remote location for storage or discharge into larger containers. This option is very beneficial when the consolidation of dust from multiple AWR units is desired.

  4. During each filter purge cycle, airflow to the filters being pulsed is momentarily redirected to the remaining filters resulting in an uninterrupted air flow. Typical time between pulses is 10 seconds. A preset solid-state timer allows adjustment of both frequency and duration of the purge pulses to fine tune the cleaning cycles for optimum performance.

  5. During the filter purging process, each reverse pulse of compressed air will discharge the dust from a single row of filters (3 filter cartridges to each row). An accumulator tank holds a 0.3 Cu. Ft. charge of air at 90 - 100 PSI for each pulse and will discharge that pulse in 0.3 sec. each time a signal is received from the filter purge control. Each accumulator tank services multiple rows of filters, pulsing one row each 10 seconds during the pulse cleaning process. The 10 second delay between pulses allows the accumulator tank to recharge for the next pulse. Because of this pulsing technique, the reverse pulse system uses only 1.8 CFM of clean, dry compressed air @ 90-110 Psig for the filter cleaning operations for every 32,000 CFM of air processed.

    Since all pulse pilot and diaphragm valves are located internally and out of the extremes of wind, rain, ice and damaging UV from direct sun, the owners of AWR modules can expect exceptional component reliability.

    Pulse system electrical requirements are 120VAC, 60 Hz, Single Phase.

CONSTRUCTON DETAILS

  1. AWR-160 Module:

    1. Construction: Structural steel frame with 14 Ga.galvanized steel skin.
    2. Overall Dimensions per module: 96"high (177" high with the Optional Drum Hopper) x 80" wide x 48" deep.
    3. Blower Motor : Dependant on process
    4. Blower Power Requirements: Dependant on process
    5. Quantity of Filter Cartridges per Module: (30)
    6. Filter Media Description: Standard (Others Available)
      Type: CX (Cellulose)
      Sq. Ft.: 240-Sq. Ft. per Filter Cartridge, Bottom (Qty 15)
    7. Air Volume Rate per Module: 16,000 CFM
    8. Total Standard Filter Surface Area: 7,200 Sq. Ft.
    9. Air to Filter Ratio: 2.2:1
    10. Shipping Weight per AWR-160: 2,100 lbs.

SPECIAL COMMENTS

Also supplied by Envirosystems:

  1. Installation, operating and maintenance manual
  2. Design engineering for ducting and plenums

AVAILABLE OPTIONAL COMPONENTS

  1. Remote fans
  2. Custom plenums
  3. Custom Ducting
  4. Integrated Control Panels for more than one module or AWR Bank
  5. On site installation supervision, start-up and training.
MODEL CART QTY CFM FILTER AREA A/F RATIO WIDTH DEPTH HEIGHT FAN SHIP WEIGHT
AWR-160 30 16,000.00 7,200 2.22:1 80 48 177 A/R 2,700
AWR-320 60 32,000.00 14,400 2.22:1 152 48 177 A/R 5,400
AWR-480 90 48,000.00 21,600 2.22:1 227 48 177 A/R 8,100
AWR-640 120 64,000.00 28,800 2.22:1 152 96 177 A/R 10,800
AWR-960 180 96,000.00 43,200 2.22:1 227 96 177 A/R 16,200

5 YEAR WARRANTY AVAILABLE

For more information please call 1-800-999-0501 or contact us